How much did chiller efficiency improve?
Specific energy consumption fell from 0.7437 kW/TR to 0.6388 kW/TR — 14.1% less electricity per ton of refrigeration — and COP rose from 4.72 to 5.50 (about +16.5%; the report states +16.67%). The chiller also produced more cooling, 831.5 TR against 724.1 TR, while drawing slightly less power.
| Parameter | Before MaxR100 | After MaxR100 |
|---|---|---|
| Chiller operating hours logged | 181.75 h | 70.5 h |
| Chiller energy consumption | 94,556 kWh | 35,192 kWh |
| Average chiller power demand | 538.53 kW | 531.19 kW |
| Chilled water entering | 14.05 °C | 14.15 °C |
| Chilled water leaving | 9.46 °C | 9.24 °C |
| Chilled water flow | 487.22 m³/h | 512.11 m³/h |
| Chilled water ΔT | 4.59 °C | 4.91 °C |
| Cooling produced | 724.11 TR | 831.50 TR |
| Average outside air temperature | 35.5 °C | 26.8 °C |
| Specific energy consumption | 0.743708 kW/TR | 0.638833 kW/TR |
| COP | 4.72 | 5.50 |
Outside air was cooler during the post-treatment logging (26.8 °C vs 35.5 °C), which also helps a water-cooled chiller through lower condenser water temperature. The report does not normalise for weather, so part of the improvement may be seasonal; we show the figures exactly as reported.
What site and chiller were treated?
Chiller No. 2 of the central chilled-water plant at a consumer-goods manufacturing plant in Yangzhou, Jiangsu Province, China.
- Site type and location
- Consumer-goods manufacturing plant, Yangzhou, Jiangsu, China
- Equipment
- Trane CVHG-1067 centrifugal water-cooled chiller, 1,100 TR (≈3,870 kW), R123 refrigerant, 36 L oil charge, 10 years old
- MaxR100 used
- MaxR100 installed in the chiller's refrigerant/oil circuit on 19 August 2022, followed by a clean-up period
- Measurement method
- Data logging of chiller power, chilled water flow and entering/leaving temperatures; cooling (TR), kW/TR and COP calculated for each period
- Measurement period
- Before: 8 Aug 2022 21:30 – 18 Aug 2022 08:15. After: 9 Sep 2022 00:15 – 16 Sep 2022 14:20
- Measured by
- The plant's own engineering department; final report 1 October 2022, quality-verified 4 October 2022
No site photographs were released for this project.
What does 14% mean in kWh and dollars?
At the pre-treatment load of 724 TR, 0.105 kW/TR less means about 76 kW lower demand — roughly 76,000 kWh saved for every 1,000 hours the chiller runs.
For a chiller running 6,000 hours a year that is about 456,000 kWh a year; at US$0.10/kWh, about US$45,600. These are RCT's illustrative calculations from the measured kW/TR, not figures from the plant report, which did not state a tariff or payback. Your own run hours and tariff decide the real number — ask us for a calculation.
Frequently asked questions
Why compare kW/TR rather than total kWh?
The before and after logging periods had different running hours and loads. kW per ton of refrigeration normalises for that, so it is the fair measure of chiller efficiency.
Does MaxR100 work in centrifugal chillers?
Yes. In this project it was used in a low-pressure R123 centrifugal chiller. It conditions internal metal surfaces and releases oil fouling from heat-transfer walls, which restores evaporator and condenser heat transfer.