Case study · MaxR100 · Manufacturing, China

MaxR100 lowered a 1,100-ton centrifugal chiller's kW/TR by 14.1% at a manufacturing plant in China

A 10-year-old 1,100-ton centrifugal chiller at a consumer-goods manufacturing plant in Yangzhou, China, needed 14.1% less power for every ton of cooling after MaxR100 treatment. Its coefficient of performance rose from 4.72 to 5.50. The plant's own engineering department logged the data.

How much did chiller efficiency improve?

Specific energy consumption fell from 0.7437 kW/TR to 0.6388 kW/TR — 14.1% less electricity per ton of refrigeration — and COP rose from 4.72 to 5.50 (about +16.5%; the report states +16.67%). The chiller also produced more cooling, 831.5 TR against 724.1 TR, while drawing slightly less power.

−14.1%kW per ton of refrigeration
4.72 → 5.50COP
+14.8%Cooling output at similar power
≈76 kWLess power at 724 TR load
ParameterBefore MaxR100After MaxR100
Chiller operating hours logged181.75 h70.5 h
Chiller energy consumption94,556 kWh35,192 kWh
Average chiller power demand538.53 kW531.19 kW
Chilled water entering14.05 °C14.15 °C
Chilled water leaving9.46 °C9.24 °C
Chilled water flow487.22 m³/h512.11 m³/h
Chilled water ΔT4.59 °C4.91 °C
Cooling produced724.11 TR831.50 TR
Average outside air temperature35.5 °C26.8 °C
Specific energy consumption0.743708 kW/TR0.638833 kW/TR
COP4.725.50

Outside air was cooler during the post-treatment logging (26.8 °C vs 35.5 °C), which also helps a water-cooled chiller through lower condenser water temperature. The report does not normalise for weather, so part of the improvement may be seasonal; we show the figures exactly as reported.

What site and chiller were treated?

Chiller No. 2 of the central chilled-water plant at a consumer-goods manufacturing plant in Yangzhou, Jiangsu Province, China.

Site type and location
Consumer-goods manufacturing plant, Yangzhou, Jiangsu, China
Equipment
Trane CVHG-1067 centrifugal water-cooled chiller, 1,100 TR (≈3,870 kW), R123 refrigerant, 36 L oil charge, 10 years old
MaxR100 used
MaxR100 installed in the chiller's refrigerant/oil circuit on 19 August 2022, followed by a clean-up period
Measurement method
Data logging of chiller power, chilled water flow and entering/leaving temperatures; cooling (TR), kW/TR and COP calculated for each period
Measurement period
Before: 8 Aug 2022 21:30 – 18 Aug 2022 08:15. After: 9 Sep 2022 00:15 – 16 Sep 2022 14:20
Measured by
The plant's own engineering department; final report 1 October 2022, quality-verified 4 October 2022

No site photographs were released for this project.

What does 14% mean in kWh and dollars?

At the pre-treatment load of 724 TR, 0.105 kW/TR less means about 76 kW lower demand — roughly 76,000 kWh saved for every 1,000 hours the chiller runs.

For a chiller running 6,000 hours a year that is about 456,000 kWh a year; at US$0.10/kWh, about US$45,600. These are RCT's illustrative calculations from the measured kW/TR, not figures from the plant report, which did not state a tariff or payback. Your own run hours and tariff decide the real number — ask us for a calculation.

How MaxR100 works All project case studies

Frequently asked questions

Why compare kW/TR rather than total kWh?

The before and after logging periods had different running hours and loads. kW per ton of refrigeration normalises for that, so it is the fair measure of chiller efficiency.