What does Radiant Climate Technologies do?
Radiant Climate Technologies (RCT) is a Singapore energy efficiency consulting and thermal engineering company. It finds where buildings, cooling plants, refrigeration and diesel fleets lose energy, then cuts the loss with HVAC heat-transfer technologies, AI HVAC optimisation, building envelope solutions and diesel fuel catalysts — and measures the result before and after. RCT also advises on government sustainability grants.
Read the full answerHow long does the Radiant+ E3 coil coating last?
The Radiant+ E3 coating is expected to last more than five years, and longer is generally expected. By protecting coils from corrosion and fouling it also extends average HVAC asset life by about three to five years.
Read the full answer
Diagnosing the problem
How do I know whether my chiller plant is using too much electricity?
Measure the plant's efficiency in kW per refrigeration ton (kW/RT): total power of chillers, pumps and cooling towers divided by the cooling load actually delivered, logged continuously for at least a week. In Singapore, a water-cooled plant built or retrofitted to current BCA rules should run at about 0.68 kW/RT or better on the water side; older plants were allowed 0.75–0.85 kW/RT. A plant regularly above 0.85 kW/RT, or an air-cooled plant above about 1.0 kW/RT, is very likely wasting electricity.
Read the full answerWhat can make an HVAC system use more energy than expected?
The usual causes are dirty or corroded coils, poor heat transfer inside chillers and pipes (oil films, scale, plain water), controls that keep equipment running harder than needed, too much airflow, chilled-water flow problems such as low ΔT, and building loads that have changed since the system was designed. Most are invisible until you measure.
Read the full answer
Reducing energy use
How can I reduce chiller and air-conditioning energy use in an existing building without replacing the whole system?
Combine operational fixes with heat-transfer restoration: optimise chiller-plant controls, restore coils, remove oil fouling from the refrigerant circuit, upgrade the chilled-water fluid, and cut solar heat gain. Measured savings for individual measures range from about 10% to over 40% of the treated system's energy, depending on its starting condition — usually with payback of one to three years.
Read the full answerWhich HVAC energy-saving measures cause the least disruption to tenants and building operations?
Controls optimisation, refrigerant-circuit treatment and heat-transfer-fluid upgrades can be done while the system keeps running. Coil cleaning and coating need each unit shut down for a few hours, so they are scheduled unit by unit, after hours or at weekends. Chiller replacement is the most disruptive option.
Read the full answerShould I optimise my existing chiller plant or replace the chillers?
Optimise first if the chillers are mechanically sound: it costs far less, causes little disruption and often pays back within one to three years. Replace when chillers are near the end of their life, repairs are frequent and expensive, they use a refrigerant that is being phased out, or measured part-load efficiency stays poor after optimisation.
Read the full answer
Specific technologies
Does coil cleaning, restoration or coating save energy, and on which equipment?
Yes, when the coils have lost heat-transfer performance to dirt, corrosion or water films. Restoring and coating coils on air-cooled chillers, AHUs, FCUs and DX/VRF units typically saves 10–25% of the unit's energy. Results depend on how degraded the coils were, the climate and operating hours — ask for metered before-and-after data, normalised for weather.
Read the full answerDo refrigerant performance enhancers work, and are they safe for compressors?
Good ones work by removing oil films from heat-transfer surfaces inside the refrigerant circuit and reducing friction, which restores heat transfer and lowers compressor power — measured gains are commonly 10–30%. Safety depends on the specific product: ask for written compatibility with your refrigerant and compressor oil, check your warranty terms, and insist on measured evidence.
Read the full answer
Checking the claims
How can I check whether an HVAC retrofit's savings and payback are credible, and how are they verified?
Credible savings are measured, not estimated: a metered baseline before the work, the same measurements afterwards, and adjustments for weather, occupancy and operating hours, following a recognised method such as IPMVP. Check payback by recomputing it yourself from the baseline kWh, the measured saving, your actual tariff and the full project cost.
Read the full answer
Regulation and funding
What must a Singapore building owner do under BCA's Mandatory Energy Improvement and Periodic Energy Audit requirements?
Under the Mandatory Energy Improvement (MEI) regime, owners of energy-intensive buildings of 5,000 m² GFA or more who receive an MEI audit notice must appoint a qualified professional, submit an energy audit and improvement plan, cut energy use intensity by 10% within three years and maintain it for a year. Under Periodic Energy Audit (PEA) rules, owners of buildings covered by BCA's cooling-system requirements must have the chilled-water plant's operating efficiency audited when BCA serves a notice. Audits and submissions must be done by a Professional Engineer (Mechanical) or a BCA-registered Energy Auditor.
Read the full answerCan I fund an energy-efficiency upgrade through grants or shared savings, with no upfront cost?
Possibly, but nothing is automatic. Grants such as BCA's GMIS-EB 2.0 and the Energy Efficiency Grant co-fund part of the cost when the building, the organisation and the project meet the current scheme rules. A shared-savings or energy performance contract can remove the upfront cost entirely: an energy services company funds the work and is repaid from the verified savings. Eligibility and terms must be confirmed with the scheme owner or contractor before you commit.
Read the full answer