HVAC energy questions · Diagnosing the problem

What can make an HVAC system use more energy than expected?

The usual causes are dirty or corroded coils, poor heat transfer inside chillers and pipes (oil films, scale, plain water), controls that keep equipment running harder than needed, too much airflow, chilled-water flow problems such as low ΔT, and building loads that have changed since the system was designed. Most are invisible until you measure.

What are the main causes, and how do I spot them?

Each cause leaves a measurable signature — check it before choosing a fix.

CauseWhat happensHow to spot itTypical fix
Fouled or corroded coilsDust, biofilm and corrosion insulate fins and block airflow; condensers reject heat at higher pressureHigh condensing pressure, high coil approach temperature, visibly damaged fins, more breakdowns in hot weatherClean, restore and coat coils — Radiant+ E3
Poor heat transfer inside the plantOil films on refrigerant-side tube walls, scale on water side, and plain water's limited heat transfer raise compressor liftRising evaporator and condenser approach temperatures; kW/RT worsening year on yearMaxR100 for oil fouling; tube cleaning; Aquene for the chilled-water loop
Incorrect controlsFixed set-points, poor chiller staging, schedules that no longer match occupancy, operators adding 'safety margin'Plant running at night or weekends; two chillers at low load; set-points never changeRe-tune controls or add AI optimisation
Excessive airflowFans run at full speed, outdoor air is over-supplied, AHU filters and coils add resistanceFan power high at low load; overcooled zones; CO₂ far below limitsFan speed control, demand-controlled ventilation, coil and filter maintenance
Water-flow issuesLow chilled-water ΔT, bypass flow, unbalanced circuits, constant-speed pumpsΔT below design; pumps at full speed; some AHUs starved while others overflowBalance and re-commission, pump speed control, valve fixes
Changed building loadsNew tenants, server rooms, longer hours or partial vacancy since designPlant sized for a different load runs inefficiently at part loadRe-stage chillers, re-set controls, review capacity before replacing
Solar heat gainSun on glass and roofs adds load to every systemWest-facing and top-floor zones hardest to coolWindow film and reflective roof and wall coatings

Why does efficiency fall so gradually that nobody notices?

Fouling, corrosion and oil build-up add a little resistance every month, and the system compensates by running longer and harder rather than failing outright.

In an independent CSIRO laboratory test, corrosion alone cut a split air conditioner's efficiency (EER) by 12.1% — while the unit still produced its cooling. See the CSIRO test. That is why a periodic efficiency measurement catches losses that comfort complaints never reveal.

Where should I start looking?

Start with measurement of plant kW/RT and ΔT, then inspect coils and check control schedules — these three cover most of the waste found in existing buildings.

Next: how to tell if your chiller plant uses too much electricity and how to cut energy use without replacing the system. The HVACR efficiency enhancement guide maps each loss to a solution.

Ask RCT to review your plant data All HVAC energy questions

Frequently asked questions

Does regular maintenance prevent these losses?

It slows them. Routine filter changes and coil washing help, but do not remove oil films inside the refrigerant circuit, restore corroded fins, or fix control logic — which is why measured efficiency often keeps drifting down.

Can a new building have these problems?

Yes. Control set-up and airflow or water balance problems are common in new buildings, and coils start fouling from the first year.

Find out how much energy your building is losing