What are the main causes, and how do I spot them?
Each cause leaves a measurable signature — check it before choosing a fix.
| Cause | What happens | How to spot it | Typical fix |
|---|---|---|---|
| Fouled or corroded coils | Dust, biofilm and corrosion insulate fins and block airflow; condensers reject heat at higher pressure | High condensing pressure, high coil approach temperature, visibly damaged fins, more breakdowns in hot weather | Clean, restore and coat coils — Radiant+ E3 |
| Poor heat transfer inside the plant | Oil films on refrigerant-side tube walls, scale on water side, and plain water's limited heat transfer raise compressor lift | Rising evaporator and condenser approach temperatures; kW/RT worsening year on year | MaxR100 for oil fouling; tube cleaning; Aquene for the chilled-water loop |
| Incorrect controls | Fixed set-points, poor chiller staging, schedules that no longer match occupancy, operators adding 'safety margin' | Plant running at night or weekends; two chillers at low load; set-points never change | Re-tune controls or add AI optimisation |
| Excessive airflow | Fans run at full speed, outdoor air is over-supplied, AHU filters and coils add resistance | Fan power high at low load; overcooled zones; CO₂ far below limits | Fan speed control, demand-controlled ventilation, coil and filter maintenance |
| Water-flow issues | Low chilled-water ΔT, bypass flow, unbalanced circuits, constant-speed pumps | ΔT below design; pumps at full speed; some AHUs starved while others overflow | Balance and re-commission, pump speed control, valve fixes |
| Changed building loads | New tenants, server rooms, longer hours or partial vacancy since design | Plant sized for a different load runs inefficiently at part load | Re-stage chillers, re-set controls, review capacity before replacing |
| Solar heat gain | Sun on glass and roofs adds load to every system | West-facing and top-floor zones hardest to cool | Window film and reflective roof and wall coatings |
Why does efficiency fall so gradually that nobody notices?
Fouling, corrosion and oil build-up add a little resistance every month, and the system compensates by running longer and harder rather than failing outright.
In an independent CSIRO laboratory test, corrosion alone cut a split air conditioner's efficiency (EER) by 12.1% — while the unit still produced its cooling. See the CSIRO test. That is why a periodic efficiency measurement catches losses that comfort complaints never reveal.
Where should I start looking?
Start with measurement of plant kW/RT and ΔT, then inspect coils and check control schedules — these three cover most of the waste found in existing buildings.
Next: how to tell if your chiller plant uses too much electricity and how to cut energy use without replacing the system. The HVACR efficiency enhancement guide maps each loss to a solution.
Frequently asked questions
Does regular maintenance prevent these losses?
It slows them. Routine filter changes and coil washing help, but do not remove oil films inside the refrigerant circuit, restore corroded fins, or fix control logic — which is why measured efficiency often keeps drifting down.
Can a new building have these problems?
Yes. Control set-up and airflow or water balance problems are common in new buildings, and coils start fouling from the first year.