Case study · MaxR100 · Restaurant, USA

MaxR100 raised cooling performance of five restaurant rooftop units in Florida by 22–32%

Five rooftop package units cooling a restaurant in Jacksonville, Florida, removed 22% to 32% more heat from the same airflow after MaxR100 was added to their refrigerant circuits. The test was run by an independent instrumentation firm before treatment, 33 days after and 70 days after.

Rooftop package units on the restaurant roof

How much did performance improve?

The enthalpy difference across each evaporator — the heat removed per pound of air — rose by 13.9% to 31.7% at the first post-treatment test and by 22.4% to 31.6% at the second. Weighted by unit size, that is about 26% and 28% more cooling from the same air flow.

+26%Capacity-weighted, 33 days after
+28%Capacity-weighted, 70 days after
62.5 tonsFive rooftop units tested
3 visitsBefore, +33 days, +70 days
Unit (size)Before 9 Jun 2009After 11 Jul 2009After 18 Aug 2009Increase (Jul)Increase (Aug)
Unit 1 (12.5 t)10.513.212.8+25.8%+22.4%
Unit 2 (12 t)10.613.714.0+29.3%+31.6%
Unit 3 (10 t)10.513.813.5+31.7%+28.2%
Unit 4 (12 t)11.112.614.1+13.9%+27.6%
Unit 5 (16 t)10.513.613.6+29.3%+29.5%

Values are evaporator enthalpy difference (return-air minus supply-air enthalpy, BTU/lb). Outdoor conditions were hotter after treatment (99 °F / 75% RH and 96 °F / 61% RH) than before (83–85 °F / 55% RH), which normally lowers performance — so the measured gain is conservative.

What site and equipment were treated?

A full-service restaurant in Jacksonville, Florida, USA, cooled by five Carrier rooftop package air-conditioning units totalling 62.5 tons (about 220 kW cooling).

Site type and location
Restaurant, Jacksonville, Florida, USA — hot, humid climate
Equipment
Five Carrier rooftop package units: 2 × 12 tons, 1 × 12.5 tons, 1 × 10 tons, 1 × 16 tons
MaxR100 used
MaxR100 refrigerant performance enhancer injected into each unit's refrigerant circuit (dosed by unit tonnage)
Pre-check
All units inspected by a qualified HVAC contractor before and after treatment
Measurement method
Return and supply air temperature and relative humidity at each evaporator → enthalpy difference; capacity = 4.5 × Δh × CFM, with airflow (CFM) constant
Measurement period
Baseline 9 June 2009; post-treatment 11 July 2009 and 18 August 2009 (40 days after the first post test)
Tested by
Independent instrumentation and testing firm, Chesapeake, Virginia; report dated 21 August 2009
Rooftop package air-conditioning units on the restaurant roof during testing
Rooftop package units during testing (from the test report)

What does a 26–28% capacity gain mean for energy and payback?

The test measured cooling output, not kWh. When each unit delivers more cooling per hour of compressor run time, it reaches set-point sooner and runs less — so energy use falls roughly in line with the capacity gain.

The report did not meter kWh or calculate dollars or payback. In other MaxR100 projects where energy was metered, savings of 16–35% were recorded; in the retail-store case payback was about six months. The report records the thermostat set-point as 74 °F at the first post-treatment test and 78 °F at the second.

How MaxR100 works All project case studies

Frequently asked questions

Why measure enthalpy instead of temperature?

Enthalpy includes both temperature and moisture. In a humid climate much of an air conditioner's work is removing moisture, so the enthalpy difference across the coil is a truer measure of cooling delivered than temperature drop alone.

Was airflow measured?

No. Airflow was assumed constant before and after, so the percentage change in enthalpy difference equals the percentage change in cooling capacity.

Find out how much energy your building is losing

Tell us about your chiller plant, AHUs, refrigeration or fleet. We will suggest what to measure first, and whether a grant could fund the work.

WhatsApp us